1 prepare controller for commissioning, Prepare controller for commissioning, 3commissioning – Lenze 8400 User Manual
Page 56: Danger

3
Commissioning
3.7
Commissioning of the "Actuating drive speed" technology application
56
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3.7.1
Prepare controller for commissioning
1. Power connection wiring
• Refer to the mounting instructions supplied with the drive controller to find help on how to
correctly design the power connections to match the requirements of your device.
2. Wire the control connections
• The assignment for your digital inputs should correspond to one of the preconfigured control
modes (
) for terminal control:
3. Connect USB diagnostic adapter.
4. Switch on voltage supply of the controller.
• Without motor operation: Connect external 24 V supply.
• With motor operation: Connect mains voltage.
If the green "DRV-RDY" LED is blinking and the red "DRV-ERR" LED is off, the controller is ready for
operation and commissioning can proceed.
Related topics:
Commissioning notes for external 24 V supply
Automatic restart after mains connection/trouble...
Assignment of the digital terminals
Control mode
DI1
DI2
DI3
DI4
Terminals 0
JOG 1/3
JOG 2/3
DCB
Cw/Ccw
Terminals 2
JOG 1/3
JOG 2/3
QSP
Cw/Ccw
Terminals 11
Cw/Ccw
DCB
MPotUp
MPotDown
Terminal 16
JOG 1/3
JOG 2/3
Cw/QSP
Ccw/QSP
Abbreviations used:
JOG Selection of fixed setpoints 1 ... 3 parameterised in
DCB Manual DC-injection braking
Cw/Ccw CW/CCW rotation
QSP Quick stop
MPotUp Motor potentiometer: Increase speed
MPotDown Motor potentiometer: Reduce speed
Cw/QSP Fail-safe selection of the direction of rotation in connection with quick stop
Ccw/QSP
Danger!
For the commissioning with motor operation observe that no setpoint is applied before
connecting the mains voltage.
In the Lenze setting, the "Inhibit at power-on" auto-start option has been deactivated
in
, i.e. the motor can directly start up if the controller is enabled after mains
connection!