I/O terminals
6.1
Digital terminals
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Internal interfaces to the application
• Relevant inputs at the
system block:
• Relevant outputs at the
system block:
Related topics:
Output of the encoder position of the DI1/DI2 frequency input
Using DI1(5) and DI2(6) as digital inputs
Using DI1(5) as counting input
Internal interfaces | System block "LS_DigitalInput"
Input
Data type
Information/possible settings
Frequency input DI1/DI2
bPosIn12_Load
BOOL
(from version 06.00.00)
Load angle integrator with starting value and reset status signal
TRUE Angle integrator is loaded with the value at dnPosIn12_Set_p and
bPosIn12_State is reset to FALSE.
dnPosIn12_Set_p
DINT
(from version 06.00.00)
Starting value for angle integrator
Output
Data type
Value/meaning
Frequency input DI1/DI2
nFreqIn12_a
| INT
Output frequency as scaled analog signal in [%]
nFreqIn12_v
| INT
Output frequency as speed signal in [inc/ms]
dnPosIn12_p
DINT
(from version 06.00.00)
Angle output signal
• 65536 [incr.] ≡ 1 encoder revolution
• Overflow is possible (display via bPosIn12_State)
bPosIn12_State
BOOL
(from version 06.00.00)
Status signal "Overflow occurred/distance processed"
• Status signal can be reset via bPosIn12_Load.
TRUE Overflow has occurred or distance is processed.
Frequency input DI5/DI6
nFreqIn56_a
| INT
Output frequency as scaled analog signal in [%]
nFreqIn56_v
| INT
Output frequency as speed signal in [inc/ms]