beautypg.com

2 signal monitoring, Signal monitoring 4, Signal monitoring ( 1304) – Lenze 8400 User Manual

Page 1304: 18 function library

background image

18

Function library

18.1

Function blocks | L_Interpolator_1

1304

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

18.1.95.2 Signal monitoring

If signal monitoring is active (

C00950/2

= 1), the signal characteristic of the dnPhIn_p input signal

is continued even if the data telegram is missing (setpoint selection via CAN).
Monitoring is performed on the basis of the dnPhIn_p position setpoint and the bSpeedAct0 status

signal:

• If the dnPhIn_p position setpoint remains the same in the next device cycle, it is either because

the speed is zero or because no data telegram has been received.

• The evaluation of the bSpeedAct0 status signal gives information about which reason applies.

This status signal needs to be transmitted by the setpoint source to ensure trouble-free

operation:

bSpeedAct0 = FALSE means that the speed is not zero, so an error is assumed: The signal

characteristic of the dnPhIn_p input signal is completed (the current slope is retained).

bSpeedAct0 = TRUE means that the speed is zero, so the unchanged position setpoint is not

treated as an error.

• If the number of missing data telegrams exceeds the limit value parameterised in

C00952

, the

bSignalError output is set to TRUE.

• The bSignalError output is automatically reset to FALSE if correct signals are detected at

dnPhIn_p and bSpeedAct0 again.

Note!

Do not change the number of interpolation steps during operation. Otherwise the

interpolation becomes inaccurate.

Note!

The nNIn_a

analog value is not monitored!