Motor control (MCTRL)
5.7
Sensorless vector control (SLVC)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.7.2.2
Torque control with speed limitation
A torque setpoint is defined for the drive system to be used during torque-controlled operation.
Unlike the
Speed control with torque limitation
, this control mode uses the speed controller for
speed limitation.
• Due to its limitation, the speed-controlled drive can only rotate within a speed range whose
positive speed is limited by nSpeedHighLimit_a and whose negative speed is limited by
nSpeedLowLimit_a.
• The speed is defined by the process.
• The torque setpoint is calculated directly from nTorqueSetValue_a.
•
From version 12.00.00 onwards,
the torque limitation is active via nTorqueMotLimit_a and
nTorqueGenLimit_a in this control mode, too, for the torque setpoint to be limited. The
torque limitation can be deactivated in
via bit 0 to obtain the previous function.
Note!
Absolute speed limitation to speed 0 min
-1
(nSpeedLowLimit_a or
nSpeedHighLimit_a = 0) is only possible
from version 12.00.00
.
Identifier
DIS code | data type
Information/possible settings
nTorqueSetValue_a
| INT
Torque setpoint / additive torque
• Scaling: 16384 ≡ 100 % M
max
nSpeedHighLimit_a
| INT
Upper speed limit for speed limitation
(only for torque-controlled operation)
• Scaling: 16384 ≡ 100 % rated speed (
nSpeedLowLimit_a
| INT
Lower speed limit for speed limitation
(only for torque-controlled operation)
• Scaling: 16384 ≡ 100 % rated speed (
)
nTorqueMotLimit_a
| INT
Torque limitation in motor mode
• Scaling: 16384 ≡ 100 % M
max
• Setting range: 0 … +199.99 %
• If keypad control is performed: Parameterisable via
nTorqueGenLimit_a
| INT
Torque limitation in generator mode
• Scaling: 16384 ≡ 100 % M
max
• Setting range: -199.99 ... 0 %