C00349 | setting - dip switch sw1, C00350 | can node address, Code – Lenze 8400 User Manual
Page 810: C00350, Or w, 16 parameter reference

16
Parameter reference
16.2
Parameter list | C00349
810
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00349
C00350
Parameter | Name:
C00349 | Setting - DIP switch SW1
Data type: UNSIGNED_16
Index: 24226
d
= 5EA2
h
DIP switch setting during last mains power-on
Display area
(min. hex value | max. hex value)
0x0000
0xFFFF
Value is bit-coded:
Bit 0 Address 1
Bit 1 Address 2
Bit 2 Address 4
Bit 3 Address 8
Bit 4 Address 16
Bit 5 Address 32
Bit 6 Address 64
Bit 7 CAN baud rate 1
Bit 8 CAN baud rate 2
Bit 9 CAN baud rate 4
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 CAN DIP switch at 24V-ON accepted
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00350 | CAN node address
Data type: UNSIGNED_8
Index: 24225
d
= 5EA1
h
Setting of the node address via parameters
• The node address can only be parameterised if the node address "0" is set via the DIP switches.
• A change in the node address will not be effective until a CAN Reset Node is performed.
Setting range
(min. value | unit | max. value)
Lenze setting
1
127 1
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1