Commissioning
3.8
Commissioning of the "Table positioning" technology application
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4. Recommendation: Set an offset in the Homing home offset input field (
the machine from stopping at an activated limit switch.
• Background: The load machine can also leave the travel range limit switch. There follows a
return to the home position that was set with the positive edge of the travel range limit
switch.
5. Set suitable profile parameters for the homing:
6. After setting the parameters for the homing, click the Back button to change back to the
Overview Signal flow dialog level.
Parameter
Lenze setting
Info
Value Unit
S-ramp time
(
0.000 s
S-ramp time for reference search/homing.
• Setting "0 s" ≡ no rounding
Start speed
(
720.0000 unit/s
Starting speed for approaching the pre-stop signals.
Start acceleration
(
720.0000 unit/s
2
Starting acceleration for the starting speed ramps.