6i/o terminals – Lenze 8400 User Manual
Page 342

6
I/O terminals
6.5
User-defined terminal assignment
342
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Example
Task: Starting from the preset technology application "Actuating drive speed" and the "Terminals 0"
control mode, the DI2 digital input is to be used for choosing an alternative
acceleration/deceleration time for the main setpoint instead of for choosing the fixed setpoint 2/3.
To do this, the DI2 digital input is not to be linked to the bJogSpeed2 input but to the bJogRamp1
input of the application module.
Procedure:
1. Use the keypad to go to the menu level Applications Actuating drive speed (conf.). This menu
level contains all the configuration parameters of the "Actuating drive speed" technology
application".
2. Navigate to the configuration parameter LA_NCtrl: bJogSpeed2 (
) which represents
the logical signal link of the application input bJogSpeed2.
Change selection "16001: DigIn_bIn2" in selection "0: Not interconnected".
4. Navigate to the configuration parameter LA_NCtrl: bJogRamp1 (
) which represents
the logical signal link of the application input bJogRamp1.
Change selection "0: Not interconnected" in selection "16001: DigIn_bIn2".
Tip!
The example shows that, for each input of the application block, the associated
configuration parameter (
) is only allowed to contain one source
that you enter.