C00085 | motor stator leakage inductance, C00087 | rated motor speed, C00088 | rated motor current – Lenze 8400 User Manual
Page 760: C00089 | rated motor frequency, C00087, C00089, Rate, C00088, C00085, Akage inductance

16
Parameter reference
16.2
Parameter list | C00085
760
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00085
C00087
C00088
C00089
Parameter | Name:
C00085 | Motor stator leakage inductance
Data type: UNSIGNED_16
Index: 24490
d
= 5FAA
h
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
mH
650.00 3.50 mH
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00087 | Rated motor speed
Data type: UNSIGNED_16
Index: 24488
d
= 5FA8
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor speed for the sensorless vector control (
Setting range
(min. value | unit | max. value)
Lenze setting
50
rpm
60000 1460 rpm
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00088 | Rated motor current
Data type: UNSIGNED_16
Index: 24487
d
= 5FA7
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Setting range
(min. value | unit | max. value)
Lenze setting
0.20
A
320.00 21.00 A
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00089 | Rated motor frequency
Data type: UNSIGNED_16
Index: 24486
d
= 5FA6
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor frequency for the sensorless vector control (
) and the servo control (
Setting range
(min. value | unit | max. value)
Lenze setting
1
Hz
1000 50 Hz
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1