C00632 | l_nset_1: max.skipfrq, C00633 | l_nset_1: min.skipfrq, C00632/1 – Lenze 8400 User Manual
Page 867: C00632/2, C00632/3, C00633/1, C00633/2, C00633/3, 16 parameter reference

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
867
16
Parameter reference
16.2
Parameter list | C00632
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00632
C00633
Parameter | Name:
C00632 | L_NSet_1: Max.SkipFrq.
Data type: INTEGER_16
Index: 23943
d
= 5D87
h
Maximum limit values for the speed blocking zones
• Selection of the maximum limit values for the blocking zones in which the speed must not be constant.
Setting range
(min. value | unit | max. value)
0.00
%
199.99
Subcodes
Lenze setting
Info
C00632/1
0.00 %
: Blocking speed1 max
C00632/2
0.00 %
: Blocking speed2 max
C00632/3
0.00 %
: Blocking speed3 max
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00633 | L_NSet_1: Min.SkipFrq.
Data type: INTEGER_16
Index: 23942
d
= 5D86
h
Minimum limit values for the speed blocking zones
• Selection of the minimum limit values for the blocking zones in which the speed must not be constant.
Setting range
(min. value | unit | max. value)
0.00
%
199.99
Subcodes
Lenze setting
Info
C00633/1
0.00 %
: Blocking speed1 min
C00633/2
0.00 %
: Blocking speed2 min
C00633/3
0.00 %
: Blocking speed3 min
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100