5motor control (mctrl) – Lenze 8400 User Manual
Page 267

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
267
5
Motor control (MCTRL)
5.11
Encoder/feedback system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Short overview of the relevant parameters:
How to parameterise the SSI encoder:
1. As encoder type (
), select "4: Absolute value encoder (SSI)".
) for SSI communication.
• For SSI protocols, the permissible baud rate is reduced if the cable length is increased. A
safe bit rate must be set, depending on the length of the used encoder cable and the
electromagnetic interference level.
3. Go to
and set the distribution of the SSI data word according to the SSI
encoder used (see the following subchapter).
4. If an SSI encoder with Gray coding is used:
Add the selection "1: Gray code" for a data conversion from Gray to binary code in
• In the Lenze setting, "0: Binary code", conversion is not performed, i.e. an SSI encoder
with binary coding is expected.
Parameter
Info
Lenze setting
Value Unit
General
SSI encoder: Coding
0: Binary code
SSI encoder: Bit rate
1: 100 kbps
Structure of the data word
Data word length
25
Bits Singleturn
13
Start bit singleturn
0
Bits multiturn
12
Start bit multiturn
13