C02879/1, 16 parameter reference – Lenze 8400 User Manual
Page 1070

16
Parameter reference
16.2
Parameter list | C02879
1070
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C02879
C02994
C02995
C02996
Parameter | Name:
C02879 | Slip calculation from equivalent circuit diagram
Data type: UNSIGNED_16
Index: 21696
d
= 54C0
h
From version 12.00.00
In order to achieve a better speed stability and torque accuracy, the slip calculation can be either derived from the
motor nameplate data (e.g. rated motor speed) or the motor equivalent circuit diagram data (stator resistance, rotor
resistance etc.).
Setting range
(min. hex value | max. hex value)
0x0000
0xFFFF
Value is bit-coded:
Info
Bit 0 SLVC
Bit 1 SC ASM
Bit 2 Reserved
Bit 3 Reserved
Bit 4 Reserved
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Bit 8 Reserved
Bit 9 Reserved
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
Subcodes
Lenze setting
Info
C02879/1
0x0000
Slip calculation from equivalent circuit diagram
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C02994 | FB xy position
Data type: UNSIGNED_32
Index: 21581
d
= 544D
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C02995 | FB display InputOutput
Data type: UNSIGNED_32
Index: 21580
d
= 544C
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C02996 | FB display InputOutput2
Data type: UNSIGNED_32
Index: 21579
d
= 544B
h
This code is for device-internal use only and must not be written to by the user!