77 l_digitallogic_1, 77 l_digitallogic_1 8, L_digitallogic – Lenze 8400 User Manual
Page 1278: L_digitallogic_1, 18 function library

18
Function library
18.1
Function blocks | L_DigitalLogic_1
1278
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
18.1.77
L_DigitalLogic_1
This FB provides a binary output signal created by a logic operation of the input signals. Optionally,
one of the constant binary values independent from the input signals can be output.
• Output of a constant binary value
• Logical ANDing of the inputs
• Logical ORing of the inputs
• Output depending on the combination of the input signals
Inputs
Outputs
Parameter
Identifier
Data type
Information/possible settings
bIn1
BOOL
Input signal 1
bIn2
BOOL
Input signal 2
bIn3
BOOL
Input signal 3
Identifier
Data type
Value/meaning
bOut
BOOL
Output signal
Parameter
Possible settings
Info
Function selection
0 "0"
Constant value "FALSE"
1 "1"
Constant value "TRUE"
2
AND operation
3
OR operation
4 bOut = f (truth table)
The output value depends on the
truth table parameterised in
/B'LJLWDO/RJLFB
E,Q
!
E2XW
&
&
&
&
E,Q
E,Q
&
bOut
bIn1 bIn2 bIn3
∧
∧
=
bOut
bIn1 bIn2 bIn3
∨
∨
=