Parameter reference
16.2
Parameter list | C00321
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00321
C00322
Parameter | Name:
C00321 | Main program runtime
Data type: UNSIGNED_16
Index: 24254
d
= 5EBE
h
Display of the current and the maximum runtime of the main program in the controller
Setting range
(min. value | unit | max. value)
0
ms
65535
Subcodes
Lenze setting
Info
C00321/1
0 ms
Curr. runtime of main program
C00321/2
0 ms
Max. runtime of main program
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00322 | Transmission mode CAN TxPDOs
Data type: UNSIGNED_8
Index: 24253
d
= 5EBD
h
TPDO transmission type according to DS301 V4.02
• The following transmission modes are supported:
• 0: Synchronous and acyclic
• 1 ... 240: Synchronous and cyclic
• 252: Synchronous - RTR only
• 253: Asynchronous - RTR only
• 254: Asynchronous - manufacturer-specific
• 255: Asynchronous - device-profile specific
• The basic setting for all PDOs is "Asynchronous - manufacturer-specific" (254).
• Illustration of the CANopen objects
...
(see DS301 V4.02).
Setting range
(min. value | unit | max. value)
0
255
Subcodes
Lenze setting
Info
C00322/1
254
Transmission mode CAN1 OUT
C00322/2
254
Transmission mode CAN2 OUT
C00322/3
254
Transmission mode CAN3 OUT
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1