Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Ck13: Error - MCKCtrlInterface function block [xx.0184.08015]
dH09: EEPROM power section [xx.0400.00009]
dH10: Fan failure [xx.0400.00016]
dH68: Adjustment data error CU [xx.0400.00104]
dH69: Adjustment data error BU [xx.0400.00105]
US01: User error 1 [xx.0980.00001]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
MCK: An error in the
function
block has occurred.
Check wiring and parameterisation of the
function block.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device fan has failed.
Possible causes:
• The short-circuit check of the fan connection has
tripped.
• The speed monitoring of the fan has tripped.
• Check the fan for short-circuit.
• Clean the fan.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
User error 1 has been tripped via the bSetError1 input of
the
system block.
User-defined.