5
Motor control (MCTRL)
5.1
Motor selection/Motor data
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
How to carry out automatic motor parameter identification:
1. Inhibit the controller if it is enabled, e.g. via the
signal at the X5/RFR terminal.
• For executing the motor parameter identification, the controller must be in the
"
2. Wait until the drive is at standstill.
3. Ensure that a motor control suitable for the motor is set in
.
4. Transfer the nameplate data to the following codes:
•
: Rated motor power
•
: Rated motor speed
•
: Rated motor current (according to the connection method /)
•
: Rated motor frequency (according to the connection method /)
•
: Rated motor voltage (according to the connection method /)
•
: Motor cos ϕ
5. Defining the motor cable length and motor cable cross-section:
•
: Motor cable length
•
: Motor cable cross-section
The resulting motor cable resistance is displayed in
.
6. Activate motor parameter identification via the
= "1: On / start" device
command.
7. Enable the controller again.
• The controller changes to the "
" device status.
• Motor parameter identification starts.
• The progress of the identification run can be seen in
• The identification is completed if the "0: Off / ready" message is displayed in
• After successful identification, it changes back to the "
" device status.
8. Inhibit controller again.