C00187 | current autofailreset processes, C00188 | autofailreset configuration, C00189 | resp. to too frequent autofailreset – Lenze 8400 User Manual
Page 788: C00189, C00187, C00188, 16 parameter reference

16
Parameter reference
16.2
Parameter list | C00187
788
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00187
C00188
C00189
Parameter | Name:
C00187 | Current AutoFailReset processes
Data type: UNSIGNED_8
Index: 24388
d
= 5F44
h
Data of the current number of "AutoFailReset" procedures
Display range
(min. value | unit | max. value)
0
16
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00188 | AutoFailReset configuration
Data type: UNSIGNED_8
Index: 24387
d
= 5F43
h
Setting which error messages are to be reset automatically.
Selection list
(Lenze setting printed in bold)
Info
0 Off
No automatic error message reset
1 Fault + TroubleQSP
Error messages with the response "Fault" and
"TroubleQSP" are reset automatically
2 WarningLocked
Error messages with the response "WarningLocked" are
reset automatically
3 All locking
All "locking" error messages are reset automatically
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00189 | Resp. to too frequent AutoFailReset
Data type: UNSIGNED_8
Index: 24386
d
= 5F42
h
Response to exceeding the maximum number of "AutoFailReset" processes set in
.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1