C00090 | rated motor voltage, C00091 | motor cosine phi, C00092 | motor magnetising inductance – Lenze 8400 User Manual
Page 761: C00093 | power section identification, C00095 | motor magnetising current, C00090, Rate, C00091, C00095, C00092

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
761
16
Parameter reference
16.2
Parameter list | C00090
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00090
C00091
C00092
C00093
C00095
Parameter | Name:
C00090 | Rated motor voltage
Data type: UNSIGNED_16
Index: 24485
d
= 5FA5
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Setting range
(min. value | unit | max. value)
Lenze setting
0
V
5000 400 V
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00091 | Motor cosine phi
Data type: UNSIGNED_8
Index: 24484
d
= 5FA4
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Setting range
(min. value | unit | max. value)
Lenze setting
0.40
1.00 0.85
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00092 | Motor magnetising inductance
Data type: UNSIGNED_16
Index: 24483
d
= 5FA3
h
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
mH
6500.0 81.0 mH
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00093 | Power section identification
Data type: UNSIGNED_16
Index: 24482
d
= 5FA2
h
Display of the identification of the detected power section of the controller
Display range
(min. value | unit | max. value)
0
65535
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00095 | Motor magnetising current
Data type: UNSIGNED_16
Index: 24480
d
= 5FA0
h
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
A
320.00 8.50 A
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100