C00118 | digoutx: inversion, C00120 | setting of motor overload (i·xt), C00122 | initial value motor overload (i·xt) – Lenze 8400 User Manual
Page 767: C00120, R load setting, C00122, C00118, 16 parameter reference
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
767
16
Parameter reference
16.2
Parameter list | C00118
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00118
C00120
C00122
Parameter | Name:
C00118 | DigOutX: Inversion
Data type: UNSIGNED_8
Index: 24457
d
= 5F89
h
The polarity of each digital output of the device can be inverted via this bit field.
Setting range
(min. hex value | max. hex value)
Lenze setting
0x00
0xFF 0x00 (decimal: 0)
Value is bit-coded: ( = bit set)
Info
Bit 0 Reserved
Bit 1 DO1 inverted
Inversion of digital output 1
Bit 2 DO2 inverted
Inversion of digital output 2
Bit 3 Reserved
Bit 4 Reserved
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00120 | Setting of motor overload (I²xt)
Data type: INTEGER_16
Index: 24455
d
= 5F87
h
Operating threshold for the "OC6: Motor overload (I²xt)" error message
• The response for reaching the threshold can be selected in
.
• The current thermal motor load is displayed in
Motor overload monitoring (I2xt)
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
250.00 100.00 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00122 | Initial value motor overload (I²xt)
Data type: UNSIGNED_16
Index: 24453
d
= 5F85
h
From version 07.00.00
The thermal motor load displayed in
is pre-initialised with the value set here when the device is connected
to the mains.
• If "100.00 %" is set, the last value at switching off the device is used for the initialisation.
• Recommended setting for operation according to UL: 50.00 %
Motor overload monitoring (I2xt)
Setting range
(min. value | unit | max. value)
0.00
%
100.00
Subcodes
Lenze setting
Info
C00122/1
0.00 %
Initial value motor overload (I²xt)
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100