11 canopen option – Lenze 8400 User Manual
Page 694
11
CANopen option
11.11
Implemented CANopen objects | I-1800
694
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Subindex 2 - transmission type
Subindex 3 - inhibit time
The entered value multiplied by 0.1 gives the delay time in [ms]. Only integers will be considered,
i.e. fractional numbers will be rounded down to integers.
Example:
• Entered value: 26
• Calculated time = 26 x 0.1 [ms] = 2.6 [ms] delay time = 2 [ms]
Subindex 5 - event timer
For cyclic operation (transmission type 254), the cycle time for sending the process data object on
the system bus can be set under subindex 5:
The entered value corresponds to the time in [ms].
PDO transmission
Transmission type
Explanation
cyclic
synchronous
event-
controlled
n = 1 ... 240
When a value n is entered, this PDO will be
accepted with every nth SYNC.
n = 252
On sync, the PDO is filled with new data, but
only sent on RTR.
n = 254, 255
Event-controlled or cyclic
Note!
The delay time can only be changed when the PDO is not active (see subindex 1, bit 31 =
1).