beautypg.com

18 function library – Lenze 8400 User Manual

Page 1323

background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

1323

18

Function library

18.1

Function blocks | L_NLim_1

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Parameter

Definition of the blocking zones
Up to three zones can be parameterised which are to be skipped by the nOut_a output signal.
The example below shows the parameter setting of two blocking zones for the L_NLim_1 FB:

[18-45] Zone masking by means of parameterisable blocking zones (in our example: L_NLim_1)

Parameter

Possible settings

Info

C00807/1...3

0.00

%

199.99 Maximum blocking frequency 1 ... 3

• Lenze setting: 0.00 %

C00808/1...3

0.00

%

199.99 Minimum blocking frequency 1 ... 3

• Lenze setting: 0.00 %

Parameter

Blocking zone 1

Blocking zone 2

Blocking zone 3

Minimum limit value

C00808/1: 48 %

C00808/2: 138 %

C00808/3: 0 %

Maximum limit value

C00807/1: 104 %

C00807/2: 178 %

C00807/3: 0 %

 Blocking zone 1

 Blocking zone 2

nOut_a [%]

nIn_a
[%]

1

0

199.99

-199.99

-199.99

199.99

C00807/1

C00808/1

48

138

0

1

104

178

C00807/2

C00808/2