6 enable controller and test application, Enable controller and test application, 3commissioning – Lenze 8400 User Manual
Page 85

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
85
3
Commissioning
3.9
Commissioning of the "Switch-off positioning" technology application
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3.9.5
Saving parameter settings safe against mains failure
The parameter set must be saved to the device safe against mains failure to prevent parameter
settings becoming lost due to mains switching.
•
Save parameter set.
3.9.6
Enable controller and test application
1.
Enable controller
• If there is no other active source for the controller inhibit, the controller changes from the
"
• The Diagnostics tab and
display all active sources for the controller inhibit.
2. Select the respective control signals via the digital inputs.
Related topics:
"Inhibit at power-on" auto-start option
Trouble-shooting during commissioning
Diagnostics & error management
Stop!
Before stipulating a speed setpoint, check whether the brake in the form of a holding
brake on the motor shaft has been released!
Note!
Observe the actual speed value (display in
.