C00104 | quick stop setting, C00105 | decel. time - quick stop, C00106 | auto dcb: hold time – Lenze 8400 User Manual
Page 764: C00105, Time parameterised in, C00104/1, C00106, 16 parameter reference

16
Parameter reference
16.2
Parameter list | C00104
764
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00104
C00105
C00106
Parameter | Name:
C00104 | Quick stop setting
Data type: UNSIGNED_16
Index: 24471
d
= 5F97
h
From version 12.00.00
Setting range
(min. hex value | max. hex value)
0x0000
0xFFFF
Value is bit-coded:
Bit 0 Standstill position-controlled
Bit 1 Ramp position-controlled
Bit 2 Reserved
Bit 3 Reserved
Bit 4 Reserved
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Bit 8 Reserved
Bit 9 Reserved
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
Subcodes
Lenze setting
Info
C00104/1
0x0000
Quick stop setting
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00105 | Decel. time - quick stop
Data type: UNSIGNED_32
Index: 24470
d
= 5F96
h
The set deceleration time determines the ramp slope at quick stop
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.900 2.000 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000
Parameter | Name:
C00106 | Auto DCB: Hold time
Data type: UNSIGNED_32
Index: 24469
d
= 5F95
h
Hold time of the automatic DC injection brake
• The DC injection brake is applied for the time set here if the value falls below the speed setpoint set in
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.000 0.500 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000