TA "Table positioning"
392
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.3.3.3
Terminals 11
When the profile is defined, the operating mode in the Lenze setting is changed simultaneously:
Connection
Assignment
Connection
Assignment
X41/DI1
LA_TabPos.bLimitSwitchPos
DO1/DO2 is only available after respective change of the function
X41/DI2
LA_TabPos.bLimitSwitchNeg
X42/DI3
-
X42/DO1
LA_TabPos.bDriveReady
X42/DI4
LA_TabPos.bPosProfileNo_2
X42/DO2
LA_TabPos.bInTarget
X43/DI5
LA_TabPos.bPosProfileNo_1
X50/A1U
LA_TabPos.nMainSetValue_a
10 V ≡ 100 % reference speed (
X43/DI6
LA_TabPos.bPosExecute
bPosProfileNo_2
(DI4)
bPosProfileNo_1
(DI5)
Selected profile
Activation of operating mode
FALSE
FALSE
0
Speed follower
FALSE
TRUE
1
Homing
TRUE
FALSE
2
Manual jog
TRUE
TRUE
3
Positioning
DI3
/DO1
DI4
/DO2
X50
GIO
GIO
GIO
DI1
DI5
n.c.
n.c.
n.c.
DI2
DI6
AR
A1U
GA
A1I
24O
+
X41
X42
X43
24O
24O
24O
+
+
+
+ 24 V
RFR
R
1k
... 10k
W
W
pos. direction
neg. direction
Limit switch
Controller enable
Speed setpoint
Start of profile generation
Bit 1
Bit 2
Profile no. 0 ... 3