C00142 | auto-start option, C00144 | switching freq. reduct. (temp.), C00142 – Lenze 8400 User Manual
Page 772: Tion, Prev, C00144, Ted via, 0 in, 16 parameter reference

16
Parameter reference
16.2
Parameter list | C00142
772
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00142
C00144
Parameter | Name:
C00142 | Auto-start option
Data type: UNSIGNED_8
Index: 24433
d
= 5F71
h
Starting performance of the controller after mains connection, undervoltage, loading of the Lenze setting as well as
a reset of "Trouble" or "Fault" can be parameterised individually.
Danger!
In the Lenze setting, the autostart option "Inhibit at power-on" is deactivated, i. e. the motor can directly start up if
the controller is enabled after mains connection!
Automatic restart after mains connection/fault...
Setting range
(min. hex value | max. hex value)
Lenze setting
0x00
0xFF 0x10 (decimal: 16)
Value is bit-coded: ( = bit set)
Info
Bit 0 Inhibit at power-on
Bit 1 Inhibit at trouble
Bit 2 Inhibit at fault
Bit 3 Inhibit at undervoltage
Bit 4 Inhibit at Lenze setting
From version 06.00.00
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00144 | Switching freq. reduct. (Temp.)
Data type: UNSIGNED_8
Index: 24431
d
= 5F6F
h
Activation of the automatic switching frequency reduction if the temperature is too high
Selection list
(Lenze setting printed in bold)
Info
0 Off
Automatic switching frequency reduction deactivated
1 On
Automatic switching frequency reduction activated
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1