C00446 | freqinxx_nout_a, C00447 | digout decoupling, C00446/1 – Lenze 8400 User Manual
Page 829: C00446/2, C00447, 16 parameter reference

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
829
16
Parameter reference
16.2
Parameter list | C00446
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00446
C00447
Parameter | Name:
C00446 | FreqInxx_nOut_a
Data type: INTEGER_16
Index: 24129
d
= 5E41
h
Display of the frequency input signals which are fed into the application.
Using DI1(5) and DI2(6) as frequency inputs
Display range
(min. value | unit | max. value)
-199.99
%
199.99
Subcodes
Info
C00446/1
FreqIn12_nOut_a
C00446/2
FreqIn56_nOut_a
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00447 | DigOut decoupling
Data type: UNSIGNED_16
Index: 24128
d
= 5E40
h
From version 02.00.00
Configuration defining the events that lead to a decoupling of the digital output terminals.
Configuring exception handling of the output terminals
Setting range
(min. hex value | max. hex value)
Lenze setting
0x0000
0xFFFF 0x0000 (decimal: 0)
Value is bit-coded: ( = bit set)
Bit 0 SafeTorqueOff
Bit 1 ReadyToSwitchOn
Bit 2 SwitchedOn
Bit 3 Reserved
Bit 4 Trouble
Bit 5 Fault
Bit 6 Reserved
Bit 7 Reserved
Bit 8 Reserved
Bit 9 Fail CAN_Management
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
Read access Write access CINH PLC STOP No transfer COM MOT