14 drive-based safety – Lenze 8400 User Manual
Page 716

14
Drive-based safety
14.4
Internal interfaces | system block "LS_SMInterface"
716
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
How to decode the I/O status information into single boolean status signals:
1. Go to the I/O level in the FB editor and connect the wIOState output of the LS_SMInterface
system block with one of the free inputs wFreeIn1 ... wFreeIn4 of the application block.
• In the following example, the wIOState output is connected with the free wFreeIn2 input
of the LA_NCtrl application block on the I/O level.
• For a better overview, all other connections of the LA_NCtrl application block are not
shown here.
2. Go to the application level and connect the selected free input wFreeIn with the wIOState
input of the L_SMStateDecoderIO_1 function block.
• The free inputs wFreeIn1 ... wFreeIn4 are outputs on the application level.
The L_SMStateDecoderIO_1 function block decodes the status signal assigned to the
wIOState input into single boolean status signals for further use in the FB interconnection.