beautypg.com

4 evaluation of the output signal, 5 comparison function "actual value = setpoint, 4 evaluation of the output signal 4 – Lenze 8400 User Manual

Page 1364: 5 comparison function "actual value = setpoint" 4, 18 function library

background image

18

Function library

18.1

Function blocks | L_PCTRL_1

1364

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

18.1.133.4 Evaluation of the output signal

After the limitation, the output signal is evaluated with the influencing factor nInfluence_a. The

evaluation is activated/suppressed along a ramp when the bEnableInfluenceRamp input is set to

TRUE. The ramp times are set with the parameters "Influence acceleration time" (

C00243

) and

"Influence deceleration time" (

C00244

).

18.1.133.5 Comparison function "Actual value = setpoint"

If setpoint and actual value are identical and there is no system deviation, the bSetEqAct status

output is set to TRUE.

• The hysteresis of the comparison function has a fixed value of 1 %.

From version 06.00.00 onwards

, the symmetrical window around the setpoint for the

comparison function can be set in

C00247

(Lenze setting: 2 %).

[18-55] Comparison function: Switching performance

[18-56] Comparison function: Example

Hysteresis (1 %, fixed value)

C00247

: Window

TRUE

FALSE

bSetEqAct

Set value

Act value

Œ 

Œ



Hysteresis (1 %, fixed value)

C00247

: Window

Act value

Set value

TRUE

FALSE

bSetEqAct

t

t

Œ





Œ