Commissioning
3.10
PC manual control
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
How to activate PC manual control:
1. If an online connection to the controller has not been established yet:
Go online.
2. Select the Application parameters tab from the Workspace.
3. Go to the Overview dialog level and click the PC manual control button.
• The following safety note is displayed first:
• Click the Cancel button to abort the action and close the dialog box.
• The Timeout monitoring input field serves to adapt the timeout for monitoring the
connection between the PC and the controller.
4. To acknowledge the note and activate PC manual control:
Click the Connect PC manual control button.
• The controller is inhibited via device command (
).
• The PC manual control operator dialog is displayed.
Note!
For activated PC manual control:
The online connection between the PC and the controller is monitored by the controller.
• If the online connection is interrupted for longer than the set timeout (Lenze setting:
2 s):
• Error response "Fault" is triggered, i.e. the motor becomes torqueless and is
coasting unless it already is at standstill.
• The "
Ck16: Time overflow manual control
" error message is entered into the
logbook.
PC manual control provides the Motion Control Kernel and the motor interface with all
required control signals and setpoint signals.
• The existing application (function block interconnection) is now decoupled from
these interfaces but will be processed as before and remains unchanged.
• It does not matter what type of motor control is set in
.