Xx.0131.00008, Xx.0131.00011, Xx.0131.00015 – Lenze 8400 User Manual
Page 600: Xx.0135.00001, Xx.0135.00002, 9diagnostics & error management

9
Diagnostics & error management
9.10
Error messages of the operating system
600
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CA08: CAN bus stopped [xx.0131.00008]
CA0b: CAN HeartBeatEvent [xx.0131.00011]
CA0F: CAN control word [xx.0131.00015]
CE1: CAN RPDO1 [xx.0135.00001]
CE2: CAN RPDO2 [xx.0135.00002]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
: The device has received the "Stop Remote
Node" NMT telegram.
Check CAN master (NMT master).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
: Cyclic node monitoring
• Being a Heartbeat consumer, the device has not
received a Heartbeat telegram from Heartbeat
producer 1 ... 15 within the defined time.
• The current states of the Heartbeat producers are
.
• Reactivate Heartbeat producers by mains switching,
restarting the controller, or a CAN Reset Node.
• Reparameterise CAN Heartbeat producer time or
switch off consumer monitoring and reset error
status if latched.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Bit 14 ("SetFail") in the wCANControl control word of the
system block has been set.
Trace back signal source on the CAN bus that sets bit 14
("SetFail").
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
: Time monitoring for RPDO1 has been
triggered.
• RPDO1 has not been received within the monitoring
time set in
or was faulty.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate electrical interference (e.g. EMC).
• Adjust monitoring time
or switch off time
monitoring.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
: Time monitoring for RPDO2 has been
triggered.
• RPDO2 has not been received within the monitoring
time set in
or was faulty.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate electrical interference (e.g. EMC).
• Adjust monitoring time
or switch off time
monitoring.