Page 603: Xx.0145.00024, Xx.0145.00025, Xx.0144.00008, Xx.0144.00009, Xx.0144.00010, 9diagnostics & error management

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
603
9
Diagnostics & error management
9.10
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PS08: Par. device invalid [xx.0144.00008]
PS09: Par. format invalid [xx.0144.00009]
PS10: Memory module binding invalid [xx.0144.00010]
dF14: SW-HW invalid [xx.0145.00014]
dF18: BU RCOM error [xx.0145.00024]
dF25: CU RCOM error [xx.0145.00025]
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The parameter set in the device is invalid.
• The error occurs while loading the parameter set.
• One code in the device is incorrect.
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The code format is invalid.
• The error occurs while loading the parameter set.
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Active device personalisation: The memory module and
the controller do not have identical binding IDs.
• Use memory modules/controllers with matching
binding IDs.
• Consult the machine manufacturer.
Note:
Lenze cannot modify e.g. a replacement device via
special access to make it work with a personalised
memory module.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.