Message, Ck08: home position unknown, Xx.0184.00156 – Lenze 8400 User Manual
Page 607: Xx.0184.08005, Xx.0184.08007, Xx.0184.08009, Xx.0184.08014, 9diagnostics & error management

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
607
9
Diagnostics & error management
9.10
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Ck08: Home position unknown [xx.0184.00156]
Ck09: Positioning mode invalid [xx.0184.08005]
Ck10: Implausible profile data [xx.0184.08007]
Ck11: Invalid operating mode [xx.0184.08009]
Ck12: Invalid profile number [xx.0184.08014]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
MCK: Home position is unknown.
Perform homing.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
MCK: The positioning mode defined via the
wPosProfileMode input is not supported.
Define a valid positioning mode.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Cause 1: The profile data result in a braking distance that
is longer than the distance to be travelled.
• Occurs if a small specified distance within a few
increments is to be positioned with final speed and S
rounding.
• It has been detected that the braking distance
required for sizing the profile phases correctly
regarding the S rounding and overchange is longer
than the selected distance in the first cycle when
bExecute = TRUE.
Cause 2: Reversing process in overchange profile linkage
• If the linkage of two profiles with final speed causes a
reversing process in the second profile and this is to
smooth another sequence profile with final speed
too, the error is set and ramped down to standstill.
Cause 3: Final speed at overchange is higher than
maximum profile speed
On cause 1:
• Set the S rounding to zero for the respective profile
and go to the next profile with final speed zero.
On cause 2:
• The continuous profile linkage with overchange must
not provide any reversing process due to the profile
selection. Here, the profile which causes a reversing
must be defined with the final speed 0.
On cause 3:
• Profiles in an overchange profile linkage with final
speeds higher than their max. profile speeds are not
supported. The final speed of a profile is limited
internally to the max. profile speed in the profile data
set.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
MCK: The operating mode defined via the
wMckOperationMode input is not supported.
Define a valid operating mode.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
MCK: The positioning profile number in the positioning
operating mode specified via the wPosProfileNo input is
invalid.
Define a valid profile number.