C00905 | motor phase direction of rotation, C00909 | speed limitation, C00910 | frequency limitation – Lenze 8400 User Manual
Page 950: C00915 | motor cable length, C00915, Motor ca, C00909/1, C00909/2, C00910/1, C00910/2

16
Parameter reference
16.2
Parameter list | C00905
950
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00905
C00909
C00910
C00915
Parameter | Name:
C00905 | Motor phase direction of rotation
Data type: UNSIGNED_8
Index: 23670
d
= 5C76
h
To correct such misconnected motor phases, the rotating field of the controller's output can be reversed by selecting
"1: Inverted". In this case, a phase will be reversed at the output of the inverter.
Note:
Up to and including version 06.00.00
, this function may only be activated for V/f characteristic control (VFCplus).
For all other motor control types, this function must not be activated because the set control mode would not work
in that case!
From version 12.00.00
, this function may be activated for all motor control types with the exception of the ones for
synchronous motor.
The activation of this function does not affect the control types for synchronous motor since these control types
require an in-phase connection of the synchronous motor.
Selection list
(Lenze setting printed in bold)
0 not inverted
1 inverted
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00909 | Speed limitation
Data type: INTEGER_16
Index: 23666
d
= 5C72
h
Max. positive/negative speed for all motor control modes
Setting range
(min. value | unit | max. value)
0.00
%
175.00
Subcodes
Lenze setting
Info
C00909/1
120.00 %
Max. pos. speed
C00909/2
120.00 %
Max. neg. speed
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00910 | Frequency limitation
Data type: UNSIGNED_16
Index: 23665
d
= 5C71
h
Max. positive/negative output frequency for all motor control modes
Setting range
(min. value | unit | max. value)
0
Hz
1000
Subcodes
Lenze setting
Info
C00910/1
1000 Hz
Max. pos. output frequency
C00910/2
1000 Hz
Max. neg. output frequency
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00915 | Motor cable length
Data type: UNSIGNED_16
Index: 23660
d
= 5C6C
h
Single motor cable length for calculating the motor cable resistance
• The calculated motor cable resistance is displayed in
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
m
1000.0 5.0 m
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10