beautypg.com

2 identifiers of the process data objects, Identifiers of the process data objects, 11 canopen option – Lenze 8400 User Manual

Page 652

background image

11

CANopen option

11.8

Process data transfer

652

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.8.2

Identifiers of the process data objects

In the Lenze setting, the identifier for process data objects PDO1 ... PDO3 consists of a so-called basic

identifier (CANBaseID) and the node address set in

C00350

:

Identifier (COB-ID) = basic identifier + node address (node ID)

• The basic identifiers of the PDOs comply with the "Predefined connection set" of DS301, V4.02.
• Alternatively, define via code

C00353

that the identifiers of the PDOs are to be assigned

according to Lenze definition or that individual settings are to be made.

• If

C00353

= "2: COBID = C0354/x", the identifiers of the PDOs can be individually set via the

Lenze codes and CANopen indexes listed in the table below. That way, identifiers

independent of the node address can be set for specific PDOs.

• If identifiers are assigned individually, all PDOs must have basic identifier values in the range

of 385 ... 1407.

Short overview: Parameters for setting the identifiers

Process data object

Basic identifier

Individual setting

dec

hex

Lenze code

CANopen index

PDO1

RPDO1

512

0x200

C00354/1

I-1400/1

TPDO1

384

0x180

C00354/2

I-1800/1

PDO2

RPDO2

768

0x300

C00354/3

I-1401/1

TPDO2

640

0x280

C00354/4

I-1801/1

PDO3

RPDO3

1024

0x400

C00354/5

I-1402/1

TPDO3

896

0x380

C00354/6

I-1802/1

Note!

After a node address change (

C00350

) and a CAN reset node afterwards, the subcodes of

C00354

automatically resume the values which result from the respective basic

identifier and the set node address.

Parameter

Info

Lenze setting

Value Unit

C00353/1

COBID source CAN1_IN/OUT

0: COBID = C0350 + CANBaseID

C00353/2

COBID source CAN2_IN/OUT

0: COBID = C0350 + CANBaseID

C00353/3

COBID source CAN3_IN/OUT

0: COBID = C0350 + CANBaseID

C00354/1

COBID CAN1_IN

0x00000201

C00354/2

COBID CAN1_OUT

0x00000181

C00354/3

COBID CAN2_IN

0x00000301

C00354/4

COBID CAN2_OUT

0x00000281

C00354/5

COBID CAN3_IN

0x00000401

C00354/6

COBID CAN3_OUT

0x00000381