Xx.0123.00094, Xx.0123.00095, Xx.0123.00096 – Lenze 8400 User Manual
Page 596: Xx.0123.00097, Xx.0123.00093, 9diagnostics & error management

9
Diagnostics & error management
9.10
Error messages of the operating system
596
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
ot2: Speed controller output limited [xx.0123.00093]
FC01: Switching frequency reduction [xx.0123.00094]
FC02: Maximum speed for Fchop [xx.0123.00095]
oC14: Direct-axis current controller limitation [xx.0123.00096]
oC15: Cross current controller limitation [xx.0123.00097]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The output of the speed controller has reached the
internal limit value. In this status, the speed controller is
not able anymore to correct the system deviation.
• Only during "Closed loop" operation or with vector
control (SLVC).
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Load-dependent switching frequency reduction
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Maximum speed for chopper frequency has been
reached.
• The maximum speed has been exceeded depending
on the switching frequency.
Select the correct maximum speed as a function of the
switching frequency.
Motor control: Determine speed limits
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Direct-axis current controller limitation is active.
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Cross current controller limitation is active.
• Observe load requirements.
• Correct dimensioning or reduce setpoint generation
dynamics if necessary.
• Check parameter setting of the current controller
with regard to the motor controllers (e.g. reduce Vp).