2 load start parameters, Load start parameters, 5drive interface – Lenze E94AxPExxxx User Manual
Page 95

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
95
5
Drive interface
5.2
Device commands
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2.2
Load start parameters
Via
= "1: Load start parameters" the start parameters of the active application can be
reloaded from the memory module to the controller:
[5-13] "Load start parameters" function
• Only possible when the application has stopped and the controller is inhibited.
• All parameter changes made since the last saving of the parameter set will get lost!
• This device command only affects the settings of the operating system, application and module
parameters, the active application remains unchanged.
Possible status displays for this device command
Related device commands
* In this example, application 1 is the active application
PS
9400
RAM
Firmware
Application 1*
PS
Application 3
PS
Application 2
PS
Memory module MM
PS
Application 1*
Status (
Meaning
99586 Device command in process
65536 Device command executed successfully
65537 General error
99371 Fault while reading the parameter set partition
99374 No memory module available
104960 CAN fault
... ...
105215 CAN fault