14.7

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Resolver: Open circuit [0x007b0018]

Motor: Calculated leakage inductance unrealistic [0x007b0019]

Absolute value encoder: Communication error [0x007b001a]

Module ID (decimal)

Error ID (decimal)

123: Motor control

24

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• Resolver cable interrupted.

• Resolver defective.

• Check resolver cable.

• Check resolver.

• Switch off the monitoring function (

C00586

="3") if no

resolver is used.

Module ID (decimal)

Error ID (decimal)

123: Motor control

25

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Faulty motor parameterisation.

Check motor parameters.

Module ID (decimal)

Error ID (decimal)

123: Motor control

26

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Absolute value encoder does not send any data or a

digital readout has been activated while the machine is

coasting down.

• Check supply cable.

• Check encoder.

• Check voltage supply (

C00421

).

• For Hiperface absolute value encoders: Check the

initialisation time (

C00412

).