12
Basic drive functions
12.14
Pole position identification
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.14.2
Parameter setting
• Parameterisation dialog in »Engineer«: Tab Application parameters Dialog level Overview
All basic functions Pole position identification
• Short overview of parameters for pole position identification:
12.14.3
Execute pole position identification
Preconditions
• The controller inhibit is active.
• The controller has the "Controller not ready" function state.
• The basic function "Pole position identification" is part of the active application.
• No other basic function is active.
Activate basic function
To request the control via the basic function, the PPI_bEnable enable input in the application must
be set to TRUE.
• If no other basic function is active, a change-over to the "Identification of pole position active"
function state is effected and an identification of pole position can be carried out via the control
inputs.
• A successful change to the function state "Pole position identification" is displayed by a TRUE
signal at the PPI_bEnabled status output.
Parameter
Info
Activation of PPI
Mode of PPI
Ppi_dnState
PolePosition Setpoint
PolePositionIdentification: Dig. signals
Highlighted in grey = display parameter