Hiperface encoder: transmission error [0x007b003a, Hiperface encoder: command error [0x007b003b, 0x007b0039 – Lenze E94AxPExxxx User Manual
Page 692: 0x007b003b, 0x007b003a, 14 diagnostics & fault analysis

14
Diagnostics & fault analysis
14.7
Error messages of the operating system
692
Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Electronic nameplate: Data outside the parameter limits [0x007b0039]
Hiperface encoder: Transmission error [0x007b003a]
Hiperface encoder: Command error [0x007b003b]
Module ID (decimal)
Error ID (decimal)
123: Motor control
57
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The motor parameters of the electronic nameplate are
outside of the limit values of the controller and therefore
cannot be accepted.
Consultation with Lenze required.
Module ID (decimal)
Error ID (decimal)
123: Motor control
58
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
• Encoder signal interferences (EMC).
• Encoder cable interrupted.
• Encoder defective.
• Faulty parameter setting of the encoder.
Note: This information is always supplied together with
the "I/O error - encoder communication" error message
and is entered in the logbook even if the encoder
monitoring is deactivated (
• Check encoder cable, use shorter encoder cable if
required.
• Check encoder.
• Check parameter setting (
).
Module ID (decimal)
Error ID (decimal)
123: Motor control
59
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
• Encoder signal interferences (EMC).
• Encoder cable interrupted.
• Encoder defective.
• Faulty parameter setting of the encoder.
Note: This information is always supplied together with
the "I/O error - encoder communication" error message
and is entered in the logbook even if the encoder
monitoring is deactivated (
• Check encoder cable, use shorter encoder cable if
required.
• Check encoder.
• Check parameter setting (
).