3 temperature monitoring of a second motor, Temperature monitoring of a second motor, 6motor interface – Lenze E94AxPExxxx User Manual
Page 273

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
273
6
Motor interface
6.9
Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.9.3.3
Temperature monitoring of a second motor
Two motor temperature sensors can be evaluated simultaneously via the two encoder inputs X7
and X8 when two motors are used (e.g. double motor for a storage and retrieval unit). For this
purpose, the selection "X7 and X8 in parallel" must be set as feedback system for the motor
• In this case, always the higher temperature of the two detected temperatures is displayed as the
current motor temperature on the Diagnostics tab and in
.
• In addition, the following display parameters exist:
•
: Motor temperature via X7
•
: Motor temperature via X8
• If one of the two detected temperatures exceeds the limit value set in
, the response set
in
is activated as advance warning.
• In the Lenze setting the "Warning" response occurs if one of the two winding temperature
exceeds 120 °C.
• As soon as one of the two detected temperatures exceeds the fixed limit value of 150 °C, the
response set in
is activated (default setting: "Fault").
• If an open circuit is detected in one of the two motor temperature sensors, the response set in
(default setting: "Fault") is activated.
• It is not possible to set different responses for the two temperature monitoring modes.
• For the motor model in the controller, the mean value of both detected temperatures is used.
Related topics:
Brake controlControl of two motor holding brakes