C00612 | resp. to can node guarding error, C00613 | resp. to can heartbeat error, C00612/1 – Lenze E94AxPExxxx User Manual
Page 828: Takes place (lenze, C00613/1, C00613, C00612, 15 parameter reference

15
Parameter reference
15.2
Parameter list | C00612
828
Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00612
C00613
Parameter | Name:
C00612 | Resp. to CAN node guarding error
Data type: UNSIGNED_8
Index: 23963
d
= 5D9B
h
Response of master if the corresponding node guarding response is not received.
"CAN on board" system bus: node guarding protocol
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
6 Information
0 No response
Subcodes
Lenze setting
Info
C00612/1
0: No response
Response to non-received telegram for monitoring entry
1 ... 32
C00612/...
C00612/32
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00613 | Resp. to CAN heartbeat error
Data type: UNSIGNED_8
Index: 23962
d
= 5D9A
h
Response if the corresponding heartbeat telegram is not received.
"CAN on board" system bus: heartbeat protocol
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
6 Information
0 No response
Subcodes
Lenze setting
Info
C00613/1
0: No response
Response to non-received telegram for monitoring entry
1 ... 32
C00613/...
C00613/32
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1