Saving of parameters failed [0x00900006, Parameter set: version conflict [0x00900007, Code number duplicated [0x00900008 – Lenze E94AxPExxxx User Manual
Page 710: 0x00900008, 0x00900009, 0x00900007, 0x00900006, 14 diagnostics & fault analysis
14
Diagnostics & fault analysis
14.7
Error messages of the operating system
710
Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Saving of parameters failed [0x00900006]
Parameter set: Version conflict [0x00900007]
Code number duplicated [0x00900008]
Parameter set: Type of standard device has been changed [0x00900009]
Module ID (decimal)
Error ID (decimal)
144: Parameter manager
6
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An error has occurred while saving the current
parameter set.
Use a different memory module.
Module ID (decimal)
Error ID (decimal)
144: Parameter manager
7
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The parameter set version on the memory module is not
compatible with the firmware of the controller.
Transfer parameter set from Engineer to the controller
and save with
Module ID (decimal)
Error ID (decimal)
144: Parameter manager
8
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Code number of the operating system has been assigned
to the application.
Eliminate error in the application and retransfer
application to controller.
Module ID (decimal)
Error ID (decimal)
144: Parameter manager
9
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The firmware has loaded a parameter set the type code
of which does not correspond to the type code of the
controller.
Load a suitable parameter set.