6
Motor interface
6.3
Adjusting motor and controller to each other
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
the reference speed of the motor must be set.
Maximum current
In
the required maximum current must be set.
• To avoid that the motor starts unintentionally without adjusting the plant data, the maximum
current in the Lenze setting is set to "0 A" in
.
Ultimate motor current I
ULT
serves to check the set ultimate motor current I
ULT
.
The ultimate motor current I
ULT
is a limit value to protect the motor from destruction or influence
of the rated data.
• This limit value must not be travelled cyclically in the drive process.
• The maximum current parameterisable in
should have a sufficient distance from this
limit value.
• If the instantaneous value of the motor current exceeds the limit value set in
the
response set in
is executed for motor protection (Lenze setting: Fault).
Maximum motor speed
Adapt the maximum motor speed in
and select the error response required when this speed
limit has been reached in
Note!
From the perspective of the application it has to be ensured that a maximum of 100 %
of the reference speed set in
is requested as speed setpoint.
Note!
When you select a Lenze motor from the catalogue and transfer the plant parameters of
the motor to the controller, the setting in
is automatically adjusted to the
selected motor.