6motor interface – Lenze E94AxPExxxx User Manual
Page 275

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
275
6
Motor interface
6.9
Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.9.4.2
Checking the individual motor phases before operation is started
A check via test signal application has been added. It injects a current into the machine before the
actual operation is started, by means of which both a motor phase failure and the existence of the
motor are checked. Only after the check has been carried out successfully, the actual operation is
continued.
• The setpoint current amplitude corresponds to the lower of the two following values:
• The test signal application is activated directly after controller enable if the following conditions
are fulfilled:
• In
a response other than "No response" is set.
• No test mode is activated (
= 0).
• No identification of pole position is active
(by device command
= "51" or "52").
• No identification procedure is active
(by device command
= "71" or "72").
• The check actuates the response set in
if one or more motor phase currents have not
reached a certain threshold value within 5 ms after controller enable.
• The threshold value depends on the device power and cannot be parameterised.
• If only one motor phase current does not reach the threshold value, "Motor phase U/V/W not
available" is entered in the logbook.
• If several motor phases do not reach the threshold value, the motor is considered as not
connected, and "Motor not connected" is entered in the logbook.
• The check is completed successfully if all three motor phase currents have exceeded the
threshold value. Then the actual operation is continued immediately.
or
Note!
• As the check is cancelled immediately if all three motor phase currents have exceeded
the threshold value, the setpoint current usually is not achieved.
• In order to be able to achieve the threshold value used for the check, the rated motor
current must at least be 10 % of the maximum device current.
• This monitoring is independent of the further rotation of the commutation angle.
50 %
2 Rated device current
⋅
⋅
50 %
2 Rated motor current
⋅
⋅