Runtime error [0x006a000d, Application has stopped [0x006a000e, Breakpoint reached [0x006a000f – Lenze E94AxPExxxx User Manual
Page 670: Faulty application parameter [0x006a0010, Division by zero [0x006a0011, 0x006a000e, 0x006a000f, 0x006a0011, 0x006a0010, 0x006a000d

14
Diagnostics & fault analysis
14.7
Error messages of the operating system
670
Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Runtime error [0x006a000d]
Application has stopped [0x006a000e]
Breakpoint reached [0x006a000f]
Faulty application parameter [0x006a0010]
Division by zero [0x006a0011]
Module ID (decimal)
Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs
13
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
A runtime error has occurred in the application. The
application processing has been interrupted.
Remove runtime error in the application and retransfer
application to controller.
Module ID (decimal)
Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs
14
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The application has been stopped using the device
="32". All user tasks are stopped.
Restart application with device command
="31".
Module ID (decimal)
Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs
15
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The application has reached a set breakpoint and the
user task with the breakpoint has stopped.
Delete breakpoint and restart application.
Module ID (decimal)
Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs
16
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An invalid parameter description is available.
Transmit application and parameter set to the controller
again.
Module ID (decimal)
Error ID (decimal)
106: Runtime environment for IEC 61131-3 programs
17
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An impermissible division by zero occurred in the
application. The division has been intercepted and the
divisor was replaced by the value "1".
Replace application.