C00142
C00150
Parameter | Name:
C00142 | Autom. restart after mains ON
Data type: UNSIGNED_32
Index: 24433
d
= 5F71
h
Starting performance of the controller after mains connection and reset of "Trouble", "Fault" or "Safe torque off
active".
Danger!
• If automatic restart is enabled (
= "1: Enabled"), the drive can restart automatically from the "Trouble"
and "Safe torque off" device states when the trouble or request for "Safe torque off active" has been eliminated!
• The controller enable generated by the application via a connection of the terminal 28 (RFR) with one of the
digital outputs DIGOUT_bOut(x) is not permissible if the following functions are active:
"Auto-start after mains ON" (
= "1") and "Program auto-start after mains switching" (
= "1")
If this is not observed, the controller can start automatically after mains connection!
Automatic restart after mains connection
Selection list
(Lenze setting printed in bold)
0 Inhibited
1 Enabled
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00150 | Status word device control 1
Data type: BITFIELD_16
Index: 24425
d
= 5F69
h
Status word 1 of the
Display area
0x0000
0xFFFF
Value is bit-coded:
Info
Bit 0 Reserved
For the meaning of bits 8 ... 11 see chapter "
".
Bit 1 Pulse inhibit active
Bit 2 Reserved
Bit 3 Reserved
Bit 4 Reserved
Bit 5 Reserved
Bit 6 Actual speed value = 0
Bit 7 Controller inhibit active
Bit 8 Device state - Bit 1
Bit 9 Device state - Bit 2
Bit 10 Device state - Bit 3
Bit 11 Device state - Bit 4
Bit 12 Warning is active
Bit 13 Trouble is active
Bit 14 Reserved
Bit 15 Reserved
Read access Write access CINH PLC STOP No transfer