The controller has two analog outputs that can be used to output internal analog signals as voltage

signals, e.g. for the control of analog indicating instruments or as a setpoint for slave drives.

9.3.1

Terminal assignment/electrical data

Note!

Initialisation behaviour:

• After mains switching until the application is started, the analog outputs remain on

0 V.

Exception handling:

• In the case of a critical exception within the application (e. g. reset), the analog

outputs are set to 0 V.

Terminal

Application

Electrical data

X3/AO1

Voltage output 1

Level: -10 V ... +10 V

(max. 2 mA)

Resolution: 11 bits + sign

Scaling: ±2

30

≡ ±10 V

Conversion rate: 1 kHz

X3/AO2

Voltage output 2

Level: -10 V ... +10 V

(max. 2 mA)

Resolution: 11 bits + sign

Scaling: ±2

30

≡ ±10 V

Conversion rate: 1 kHz

X3/GA

Reference potential (analog ground)

GA

AO1

AO2

X3