C00159 | quick stop by (source), C00162 | masked error number, C00166 | error description – Lenze E94AxPExxxx User Manual
Page 775: C00159, C00166, 15 parameter reference

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
775
15
Parameter reference
15.2
Parameter list | C00159
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00159
C00162
C00166
Parameter | Name:
C00159 | Quick stop by (source)
Data type: BITFIELD_16
Index: 24416
d
= 5F60
h
Display area
0x0000
0xFFFF
Value is bit-coded:
Bit 0 Reserved
Bit 1 Reserved
Bit 2 Reserved
Bit 3 Reserved
Bit 4 Application
Bit 5 Device command
Bit 6 Error response
Bit 7 Internal PLC
Bit 8 Reserved
Bit 9 Reserved
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00162 | Masked Error number
Data type: UNSIGNED_32
Index: 24413
d
= 5F5D
h
From software version V2.0
Display of the individual components of the error number shown in
Display range
(min. value | unit | max. value)
0
4294967295
Subcodes
Info
C00162/1
Module ID + error number
• As described in the chapter "
".
C00162/2
Instance number
C00162/3
Error response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00166 | Error description
Data type: VISIBLE_STRING
Index: 24409
d
= 5F59
h
Error description for error number indicated in
Read access Write access RSP PLC-STOP No transfer
Scaling factor: 1
Character length: 64