C00107 | ref. for quick stop dec. time, C00114 | dig. input x: terminal polarity, C00118 | dig. output. x: terminal polarity – Lenze E94AxPExxxx User Manual

Page 768: C00120 | mot. overload protection (i·xt), Reshold set in, C00120, C00114, Terised in, C00118, Into

background image

15

Parameter reference

15.2

Parameter list | C00107

768

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00107

C00114

C00118

C00120

Parameter | Name:

C00107 | Ref. for quick stop dec. time

Data type: UNSIGNED_8

Index: 24468

d

= 5F94

h

Reference for the deceleration time set in

C00105

.

Basic function "

Quick stop

"

Selection list

(Lenze setting printed in bold)

0 Motor reference speed (C00011)
1 Current speed

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00114 | Dig. input x: Terminal polarity

Data type: UNSIGNED_8

Index: 24461

d

= 5F8D

h

"0" = positive logic (HIGH level = TRUE, LOW level = FALSE)

"1" = negative logic (HIGH level = FALSE, LOW level = TRUE)
Setting range

(min. value | unit | max. value)

0

1

Subcodes

Lenze setting

Info

C00114/1

0

Terminal polarity - digital input 1 ... 8

C00114/...
C00114/8

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00118 | Dig. output. x: Terminal polarity

Data type: UNSIGNED_8

Index: 24457

d

= 5F89

h

"0" ≡ positive logic (TRUE ≡ HIGH level, FALSE ≡ LOW level)

"1" ≡ negative logic (FALSE ≡ HIGH level, TRUE ≡ LOW level)
Setting range

(min. value | unit | max. value)

0

1

Subcodes

Lenze setting

Info

C00118/1

0

Terminal polarity - digital output 1 ... 4

C00118/...
C00118/4

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00120 | Mot. overload protection (I²xt)

Data type: UNSIGNED_32

Index: 24455

d

= 5F87

h

Threshold for I

2

x t disconnection

• Disconnection is carried out if the thermal motor load (

C00066

) is higher than the set threshold.

• A 100 % thermal motor load corresponds to a permanently flowing rated motor current

Note:

When the value is parameterised to 200 %, the monitoring mode of the motor overload protection is switched off!

I2xt motor monitoring

Setting range

(min. value | unit | max. value)

Lenze setting

0

%

200 105 %

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1