CAN module (MXI1): Basic configuration invalid [0x009d0002]
CAN module (MXI1): Heartbeat error index 1 ... 32 [0x009e0000 ... 0x009e001f]
CAN module (MXI1): Lifeguarding error [0x009e0020]
Module ID (decimal)
Error ID (decimal)
157: CAN module in MXI1: CAN dispatcher
2
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI1:
Configuration error
• Faulty download of an Engineer or PLC Designer
project
• Invalid CAN settings according to DS301V402 in the
Engineer or PLC Designer.
• Repeat download
• Correct CAN settings in the project and regenerate
project.
Module ID (decimal)
Error ID (decimal)
158: CAN module in MXI1: CAN-NMT handler
0 ... 31
Response (Lenze setting printed in bold)
Setting:
C13613/1...32
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI1: Cyclic node
monitoring
• Node station has not received a heartbeat telegram
from node 1 ... 32 within the defined time.
• Reactivate CAN node by mains switching, restart of
the controller (
="11000") or CAN reset node.
• Select a different heartbeat producer monitoring
time or switch off monitoring and reset locked error
status, if necessary.
Tip: Save the current parameter set before mains
switching and restart of the controller (
="11").
Module ID (decimal)
Error ID (decimal)
158: CAN module in MXI1: CAN-NMT handler
32
Response (Lenze setting printed in bold)
Setting:
C13614
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI1: Cyclic node
monitoring
• Slave response: Maximum time between two node
guarding telegrams (remote transmission request
telegram) from the master has been exceeded.
Select a different Lifeguarding monitoring time or switch
off monitoring.