8
Braking operation
The 9400 ServoPLC as a single-axis controller (Single Drive) is provided with an integrated brake
transistor.
• The required brake resistor must be connected externally (see Mounting Instructions/Hardware
Manual).
• The rated values for the internal brake transistor are given in the Hardware Manual in the
chapter "Rated data".
Stop!
If the brake resistor actually connected is smaller than the brake transistor
parameterised, the brake chopper can be destroyed!
The brake resistor can be thermally overloaded. Carry out protective measures suitable
for the installation, e.g.:
• Parameterisation of an error response in
and evaluation of the parameterised
error message within the application or within the machine control.
• External interconnection using the thermal contact on the brake resistor (e.g. supply
interruption via the mains contactor and activation of the mechanical brakes).
Note!
The brake chopper control is also guaranteed if, for example, the application stands still
or the 24-V supply is not connected and the controller is only fed by the DC bus.